Gentlemen, we are connecting field H2S sensor and detector to a control room located 700m (2296.6 ft) away from the instrument. The design cable selection is 18 AWG 16pr for digital signals and 18 AWG 4TR for analog signals.
Now we are facing voltage drop, and the field instrument is not functioning. How to solve this issue without replacing the cables with 14 AWG?
Sensor/detector module: General Monitors S4000TH and S5000.